Carrier · Heat pump troubleshooting
Prepare the control boards for voltage and signal checks
What is going on
Measurements at the indoor or outdoor control board need the power handled in a set order and anti-static protection.
Check in this order
- Disconnect the main power.
- Check the outdoor board first when possible. Remove the outdoor unit top cover.
- Reconnect the main power and probe the board inputs and outputs with a digital multimeter, using the wiring diagrams.
- Connect the red probe to the hot signal and the black probe to ground or negative.
- Note that some DC signals are pulsing. The pulse should move steadily whenever a signal is present.
- To check the indoor board, disconnect the main power, remove the front cover and then the control box cover.
- Lift the indoor board out, place it face up on a plastic surface (not metal), reconnect power and repeat the measurements.
- Disconnect the main power again before touching the board.
- Wear anti-static gloves or a wrist strap while handling the board. Follow lockout procedures.
Applies to: D5FCFAH indoor and outdoor control boards
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FCFAH service manual, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.