Daikin · Heat pump troubleshooting

Power supply waveform check (Check 11)

FTXM-W/V

What is going on

Checks the incoming supply waveform for distortion that can upset the inverter.

Likely causes

  • Supply disturbance near the zero crossing
  • Poor supply quality

Check in this order

  1. Measure the supply waveform between terminal strip No. 1 and No. 2.
  2. Confirm the waveform is a clean sine wave.
  3. Look for disturbance near the zero crossing.
  4. If the waveform is distorted, correct the power supply before replacing parts.

Applies to: Power supply to indoor and outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 147. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.