Daikin · Heat pump troubleshooting

Power module check (Check No.22)

FTXM-W/V

What is going on

Checks the power module for shorts by measuring resistance to the compressor terminals.

Likely causes

  • Short in the power module (resistance near 0 Ω)

Check in this order

  1. Confirm the voltage between (+) and (-) of the power module is about 0 V before checking.
  2. Disconnect the compressor harness connector from the outdoor unit PCB. Press the protrusion on the connector to release it.
  3. Measure resistance between the power module (+) and (-) terminals and the compressor terminals U, V, W, in both polarities, using the table in the manual.
  4. If the resistance is normal (several kΩ to several MΩ), the power module is OK.
  5. If the resistance is near 0 Ω or shorted, the power module is NG.
  6. 09/12 class PCB pin map pin 24 +, pin 23 U, pin 22 V, pin 21 W, pin 20 -.

Applies to: Outdoor unit power module and compressor terminals

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 157. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.