Daikin · Heat pump troubleshooting
Power module check (Check No.22)
What is going on
Checks the power module for shorts by measuring resistance to the compressor terminals.
Likely causes
- Short in the power module (resistance near 0 Ω)
Check in this order
- Confirm the voltage between (+) and (-) of the power module is about 0 V before checking.
- Disconnect the compressor harness connector from the outdoor unit PCB. Press the protrusion on the connector to release it.
- Measure resistance between the power module (+) and (-) terminals and the compressor terminals U, V, W, in both polarities, using the table in the manual.
- If the resistance is normal (several kΩ to several MΩ), the power module is OK.
- If the resistance is near 0 Ω or shorted, the power module is NG.
- 09/12 class PCB pin map pin 24 +, pin 23 U, pin 22 V, pin 21 W, pin 20 -.
Applies to: Outdoor unit power module and compressor terminals
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 157. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.