Outdoor unit will not run - HK32EA defrost board heat pumps

What is going on

So the thermostat is calling for cooling or heat, but the outdoor unit won't come on. That is a good one to work down with a meter, because the circuit is a simple chain. This applies to Carrier and Bryant single-stage heat pumps with an HK32EA defrost board. The call comes in on Y, runs through the pressure switches on the board, and goes out to the contactor coil. Find where the 24 V stops and you have found the problem. Remember some boards also have a five-minute delay.

Likely causes

  • No Y signal from thermostat
  • Open pressure switch
  • 5-minute delay still timing (003/008)
  • Failed contactor
  • Capacitor or compressor fault

Check in this order

  1. Measure 24 V at the Y input, none means thermostat or wiring
  2. Check 24 V on the board Y spade, this feeds the pressure switches and returns to T1
  3. On 003/008 boards the time delay may be active, simply wait it out, or use the speed-up pins for no more than 1 s as the manual describes, then recheck
  4. Look for 24 V at the contactor coil from T2, none points to an open pressure switch, and the switch should be tested, not bypassed
  5. Coil has 24 V but contactor open: replace the contactor
  6. Contactor closed but nothing runs with power off, check wiring, capacitor and compressor
  7. High voltage and refrigerant work belong to a licensed technician

Applies to: Carrier/Bryant single-stage heat pumps with HK32EA001/007/003/008/009/010/011

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), Troubleshooting (HK32EA001/007 and 003/008). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.