Carrier · Heat pump troubleshooting
Outdoor unit unresponsive after several faults
What is going on
Carrier Infinity 18VS variable speed heat pump (25VNA8) can stop responding after certain combinations of earlier fault codes, even though nothing is actually broken.
Likely causes
- Control latched up after earlier faults, not a failed part
Check in this order
- Turn off high voltage to the outdoor unit for at least 2 minutes, then restore power, because that clears the latch. Use the disconnect.
- Expect the 10-minute sump warm-up delay after power-up (code 68) before full operation, so do not read that as a new fault.
- If the unit still does not respond, troubleshoot with the STATUS light codes.
- Write down any codes that show before you cycle power so you can chase repeat faults.
Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Status Codes note p.14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.