Outdoor unit: remove sound blankets, stop valve plate and compressor
What is going on
Heat pump compressor removal. Brazing requires protection from heat damage.
Check in this order
- Remove the 6 screws and the stop valve mounting plate. Remove the conduit tube if connected.
- Remove the top sound blanket.
- Remove the body sound blanket.
- Remove the terminal cover.
- Disconnect the compressor lead wires and note the U, V, W positions.
- Remove the overload (OL) and its retainer, then route the OL lead wire.
- Remove any putty, the terminal cover and other plastic parts that could burn.
- Protect the surroundings with a protective sheet or steel plate.
- Heat and disconnect the brazed compressor piping, keeping the piping within the allowed slit range.
- Remove the 2 nuts securing the compressor.
Applies to: 3.5 to 5.0 ton HP models only
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EB service instructions, p. 118-120. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.