Daikin · Heat pump troubleshooting
Outdoor unit: remove solenoid, four-way and EEV coils
What is going on
Removal of the valve coils from the outdoor unit control valves. Torque values are in the matching setting table.
Check in this order
- Cut the 2 clamps on the solenoid valve coil lead wire.
- Remove the 2 screws and take off the solenoid valve coil.
- Remove the 1 screw and take off the four-way valve coil.
- Cut the clamp and pull out the electronic expansion valve coil.
- Tighten fasteners to the torque values listed for each coil when reassembling.
Applies to: Solenoid valve, four-way valve and electronic expansion valve coils; the EEV coil and four-way coil removal applies to 3.5 to 5.0 ton HP models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EB service instructions, p. 112. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.