Daikin · Heat pump troubleshooting

Outdoor unit PCB abnormality, code E1

FTXM-WFTXM-V

What is going on

The outdoor PCB microprocessor is not running correctly, or the zero-cross signal is not detected.

Likely causes

  • Defective outdoor unit PCB
  • Noise
  • Momentary voltage drop
  • Momentary power failure

Check in this order

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check whether the outdoor unit is grounded. If not, ground the system.
  3. Investigate the cause of noise. The cause may be external to the unit.
  4. Turn the power on.
  5. If the error returns, replace the outdoor unit PCB (main PCB).

Applies to: Inverter pair wall mounted FTXM-W/V, outdoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 116. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.