Daikin · Heat pump troubleshooting
Outdoor unit PCB abnormality, code E1
What is going on
The outdoor PCB microprocessor is not running correctly, or the zero-cross signal is not detected.
Likely causes
- Defective outdoor unit PCB
- Noise
- Momentary voltage drop
- Momentary power failure
Check in this order
- Turn off the power switch before connecting or disconnecting any connector.
- Check whether the outdoor unit is grounded. If not, ground the system.
- Investigate the cause of noise. The cause may be external to the unit.
- Turn the power on.
- If the error returns, replace the outdoor unit PCB (main PCB).
Applies to: Inverter pair wall mounted FTXM-W/V, outdoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 116. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.