Daikin · Heat pump troubleshooting
Outdoor main PCB (A1P) connector map, 18/24 class
What is going on
S: indoor-outdoor transmission terminal block. S20: electronic expansion valve coil (white). S40: overload protector and high pressure switch. S70: DC fan motor. S80: four-way valve coil. S90: thermistors (outdoor air, outdoor heat exchanger, discharge pipe, liquid pipe). S201 and S202: harness to the service monitor PCB (A2P). CK1: harness for the voltage endurance test. HL1 and HN1: power supply terminal block harness. E1 and E2: earth/ground harness. U, V, W: compressor harness. FU1 and FU2: fuses. FU3: fuse. V2, V3 and V401: varistors.
Check in this order
- Use this map to find the matching connector before testing or replacing a wire harness.
- Check the fuse ratings listed for FU1, FU2 and FU3 before replacing a fuse.
Applies to: Outdoor unit main PCB (A1P), 18/24 class
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.