Daikin · Heat pump troubleshooting
Outdoor fan system check (Check No.19, DC motor)
What is going on
Checks whether the outdoor fan runs and whether its lead connector is connected.
Likely causes
- Fan motor lead wire connector disconnected
Check in this order
- Check whether the outdoor fan is running.
- If it is running, the outdoor fan system is functioning.
- If it is not running, check whether the fan motor lead wire connector is disconnected. If so, reconnect it.
- If the connector is connected and the fan still does not run, go to Check No.16 (outdoor fan motor check).
Applies to: Outdoor unit DC fan system
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.