Daikin · Heat pump troubleshooting

Outdoor fan motor check (Check No.16)

FTXM-W/V

What is going on

Checks the outdoor fan motor and its control signals. The 09/12 class and 18/24 class use different test points.

Check in this order

  1. 09/12 class with power off, rotate the fan motor by hand once and check for a sinusoidal voltage between pins 1-3 and 3-5.
  2. 18/24 class set operation OFF and power OFF, then disconnect connector S70.
  3. 18/24 class check for 320 VDC between pins 4-7 (should be 320 VDC).
  4. 18/24 class check for 15 VDC control voltage between pins 3-4.
  5. 18/24 class check for a rotation command of 0 to 6.5 VDC between pins 2-4.
  6. Keep operation OFF and power OFF, then reconnect S70.
  7. 18/24 class rotate the fan motor one turn by hand and check for 4 pulses (0 to 15 VDC) at pins 1-4.
  8. If the fuse has blown, check the fan motor for proper function.
  9. If step 2 (320 VDC) is NG, replace the outdoor unit PCB (main PCB).
  10. If step 4 (rotation command) is NG, the Hall IC is defective: replace the outdoor fan motor.
  11. If both steps 2 and 4 are OK, replace the outdoor unit PCB (main PCB).

Applies to: Outdoor unit fan motor, 09/12 and 18/24 class

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 152. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.