Daikin · Heat pump troubleshooting
Outdoor fan motor check (Check 16)
What is going on
Checks the outdoor fan motor drive and the Hall IC signal. The check differs by class.
Likely causes
- Blown fuse
- Faulty outdoor fan motor
- Faulty Hall IC in the fan motor
- Faulty outdoor unit main PCB
Check in this order
- 09/12 class turn the fan by hand once. Check that a sinusoidal voltage appears between pins 1-3 and 3-5.
- 18/24 class set operation off and power off. Disconnect connector S70.
- Check that the voltage between pins 4-7 is 320 VDC (within 320 ±30 V).
- Check that the control voltage between pins 3-4 is 15 VDC.
- Check that the rotation command voltage between pins 2-4 is 0 to 6.5 VDC.
- Connect S70 again with power off. Turn the fan by hand one turn and check for 4 pulses (0 to 15 VDC) at pins 1-4.
- If the fuse is blown, check the fan motor before replacing the fuse.
- If pins 4-7 are out of range, replace the outdoor unit main PCB.
- If pins 2-4 are out of range, the Hall IC is faulty; replace the outdoor fan motor.
- If both checks are good, replace the outdoor unit main PCB.
Applies to: Outdoor fan motor, 09/12 and 18/24 class
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 152. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.