Carrier · Heat pump troubleshooting

Outdoor ECM fan not running - Carrier 25HNB9/24ANB1

What is going on

Compressor is running but the variable-speed outdoor fan on the Carrier 25HNB9 or 24ANB1 stays off. That is a short trip to a hot compressor and high head pressure, so don't leave it running. Split the problem into power to the motor, signal from the board, and the motor itself. Fast fix is usually a loose plug.

Likely causes

  • No 230 V to the motor
  • No PWM signal from the board
  • Loose motor connections
  • Failed motor

Check in this order

  1. Confirm 230 V is present at the motor (power on, unit need not run), line voltage so use care
  2. With the motor unplugged, read DC volts across PWM1 and PWM2 against the PWM table
  3. No signal check board connections, then replace the board
  4. Signal present reconnect the motor and recheck, if the signal drops or the motor ignores it, check connections then replace the motor
  5. Bench check with PWM wires off the board, 24 VAC on the PWM leads should run the motor at full speed
  6. Shut the unit off if the fan will not run and the compressor keeps going, to protect the compressor

Applies to: 25HNB9, 24ANB1

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), ECM Fan Motor Troubleshooting. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.