Outdoor DC fan motor check (controller in outdoor PCB)
What is going on
Used to decide between replacing the fan motor and replacing the PCB.
Check in this order
- Disconnect the UVW connector.
- Measure resistance between U-V, U-W and V-W.
- If the three resistances are not equal, replace the fan motor.
- If they are equal, replace the PCB.
Applies to: D5CURA outdoor DC fan motor
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5CURA service manual, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.