Daikin · Heat pump troubleshooting

Outdoor coil thermistors used for defrost

DX6VSDZ6VS

What is going on

The control board uses two outdoor thermistors for defrost: the outdoor coil thermistor (Tm) on the return bend entering the coil, and the outdoor coil defrost thermistor (Tb) at the bottom flowrator leg at the coil outlet.

Check in this order

  1. Locate Tm on the return bend entering the outdoor coil.
  2. Locate Tb on the bottom flowrator leg at the coil outlet.
  3. Check the readings against the thermistor resistance tables in this manual when diagnosing defrost problems.

Applies to: Outdoor heat pump coils

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.