Daikin · Heat pump troubleshooting
Opening and closing the stop valves
What is going on
Stop valves ship closed. They must be opened before start-up. Inadequate torque can leak refrigerant. The 3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity units use a back sealing type valve, so the back seal must be closed as in the opening procedure. Torque values are in the stop valve tables.
Likely causes
- Stop valve left closed at start-up
- Insufficient tightening torque causing leakage
Check in this order
- Remove the valve lid and turn the valve counterclockwise with a hex wrench to open.
- Turn until the shaft stops.
- Then turn until the designated torque is reached, as in the stop valve table.
- Refit the valve lid.
- To close, remove the valve lid and turn clockwise until the shaft stops.
- Then tighten to the designated torque, and refit the valve lid.
- On back-sealing valves, seal the back seal as in opening step 3.
- Make sure both liquid and gas stop valves are open before start-up.
Applies to: Liquid and gas stop valves on DX6VS / DZ6VS / DZ6VSA units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.