Daikin · Heat pump troubleshooting
Non-condensable in the system
What is going on
Non-condensable gas raises the pressure above what the coil temperature supports.
Likely causes
- Air or other non-condensable gas in the system
Check in this order
- Shut the system down and let pressures equalize for at least 15 minutes.
- Compare the pressure with the temperature of the coldest coil, where most refrigerant collects.
- If the pressure corresponds to a higher temperature than the coil, non-condensable is present.
- Remove the charge, replace or install the liquid line drier, evacuate and recharge.
Applies to: Refrigerant circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.