Non-condensable in the system

DX6VSDZ6VS

What is going on

Non-condensable gas raises the pressure above what the coil temperature supports.

Likely causes

  • Air or other non-condensable gas in the system

Check in this order

  1. Shut the system down and let pressures equalize for at least 15 minutes.
  2. Compare the pressure with the temperature of the coldest coil, where most refrigerant collects.
  3. If the pressure corresponds to a higher temperature than the coil, non-condensable is present.
  4. Remove the charge, replace or install the liquid line drier, evacuate and recharge.

Applies to: Refrigerant circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.