Daikin · Heat pump troubleshooting

Network communication troubleshooting

DX6VS / DZ6VSDV**FEC / DFVE**CAPE(A)* / CHPE*

What is going on

Use this when a network communication error code has occurred. Red communications LED on the control board: off means normal; 1 flash means communications failure (unknown packet or communication failure); 2 flashes means out-of-box reset (control power up or learn button pressed). Green receive LED: off means no power or communication error; steady flash means no network found (broken or disconnected communication wire, or unit installed as legacy/traditional system); rapid flashing means normal network traffic; solid on means a terminal 1/terminal 2 miswire (reversed at indoor unit, thermostat or outdoor unit, or shorted to each other or to terminal C or R).

Likely causes

  • Terminal 1 and terminal 2 wires reversed
  • Short between terminal 1 and terminal 2, or between either and terminal C (24VAC) or R (24VAC, COM)
  • Broken or damaged wire at a terminal, inside a wire nut, or in the cable between units
  • No power to the unit or an open fuse
  • Unit installed as legacy/traditional system instead of communicating

Check in this order

  1. Confirm the low voltage wiring matches the installation instructions and check for miswiring (for example, terminal 1 and 2 reversed).
  2. Check wires for damage, including broken wires at terminals, inside wire nuts, or in the cable between units.
  3. Run a continuity check on the wires and replace the cable if needed.
  4. Check circuit breakers and fuses and reset or replace if needed.
  5. Check for shorts in the low voltage wiring.
  6. Change both DS1 dip switches on the outdoor unit control board to the opposite position.
  7. Restart the system outdoor unit first, then indoor unit. Check whether the error codes have cleared.
  8. Confirm the installation type (legacy/traditional or communicating) if the green LED shows a steady flash.

Applies to: Outdoor unit control board (H1P, H2P, H3P) and indoor unit control board (H2P, H3P)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.