Mode display overview (7-segment board display)

FIT

What is going on

The 3-digit display on the outdoor unit PCB is a backup to the thermostat for reading faults, fault history, monitoring and setting the unit. It has five screens: Screen 0 shows the present fault (default screen), Screen 1 the fault history (6 recent faults), Screen 2 monitoring, Screen 3 Setting Mode 1 and Screen 4 Setting Mode 2. The display blinks at 0.4 s on and 0.4 s off. Buttons are RECALL, TEST and LEARN.

Check in this order

  1. Use RECALL to move forward through the screens and items.
  2. Use TEST to confirm or change a setting.
  3. Use LEARN to return to Screen 0.

Applies to: FIT outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FIT outdoor unit installation & service reference, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.