Daikin · Heat pump troubleshooting
Measuring capacitor residual voltage before service
What is going on
Check that the inverter capacitor voltage has dropped before touching charged parts.
Check in this order
- Shut down the power and leave the control box for 10 minutes.
- Touch the earth ground terminal to release static from your body.
- Measure DC voltage between C+ and C- with a VOM on the DC voltage range.
- Confirm the reading is 50 V or less before touching the charged area.
- Disconnect the outdoor fan motor connectors right after measuring, since wind on the fan blade can recharge the capacitor.
Applies to: DX6VS/DZ6VS outdoor unit (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity FIT)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.