Measuring capacitor residual voltage before service

DX6VSDZ6VS

What is going on

Check that the inverter capacitor voltage has dropped before touching charged parts.

Check in this order

  1. Shut down the power and leave the control box for 10 minutes.
  2. Touch the earth ground terminal to release static from your body.
  3. Measure DC voltage between C+ and C- with a VOM on the DC voltage range.
  4. Confirm the reading is 50 V or less before touching the charged area.
  5. Disconnect the outdoor fan motor connectors right after measuring, since wind on the fan blade can recharge the capacitor.

Applies to: DX6VS/DZ6VS outdoor unit (3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity FIT)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.