Daikin · Heat pump troubleshooting
Main circuit short check (Check No.20)
What is going on
Checks the diode bridge DB1 for a short on the main circuit. Confirm the DC voltage is about 0 V before testing.
Likely causes
- Short circuit on the main circuit
Check in this order
- Confirm the voltage between (+) and (-) of diode bridge DB1 is about 0 V before checking.
- Measure the resistance between the DB1 pins in both polarities using the table in the manual.
- If the resistance is normal (several kΩ to several MΩ), the main circuit is OK.
- If the resistance is very low (about 1 kΩ or less, per the manual), a short circuit is present on the main circuit.
Applies to: Outdoor unit main circuit / diode bridge DB1
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.