Daikin · Heat pump troubleshooting

Main circuit short check (Check No.20)

FTXM-W/V

What is going on

Checks the diode bridge DB1 for a short on the main circuit. Confirm the DC voltage is about 0 V before testing.

Likely causes

  • Short circuit on the main circuit

Check in this order

  1. Confirm the voltage between (+) and (-) of diode bridge DB1 is about 0 V before checking.
  2. Measure the resistance between the DB1 pins in both polarities using the table in the manual.
  3. If the resistance is normal (several kΩ to several MΩ), the main circuit is OK.
  4. If the resistance is very low (about 1 kΩ or less, per the manual), a short circuit is present on the main circuit.

Applies to: Outdoor unit main circuit / diode bridge DB1

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 154. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.