Low-voltage or over-voltage detection: troubleshooting flow (continued)
What is going on
Flowchart for the power supply check that follows section 4.8. The code number for this flow is not printed on these pages. Page 112 text is jumbled, so the order below is approximate. Verify the sequence against the full flowchart before relying on it.
Likely causes
- Power supply voltage outside tolerance
- Loose or disconnected harness
- Electrical noise or disturbance on the supply
- Failed indoor or outdoor PCB
- Outdoor fan motor fault
Check in this order
- Turn off the power switch before connecting or disconnecting any connector.
- Reconnect any loose or disconnected harness.
- Check the supply voltage. It must be within ±10% of the rated value.
- Correct the power supply if voltage is out of range.
- Turn the power off for at least 30 seconds before turning it on again.
- Turn the power on and check whether the system restarts. Repeat a few times.
- If the error returns within 3 minutes of power-on, replace the indoor unit PCB (control PCB).
- Check the outdoor fan. If it does not turn smoothly, replace the outdoor fan motor and the outdoor unit PCB (main PCB).
- If the fault persists, replace the outdoor unit PCB (main PCB).
- Check for longer-term disturbance factors such as noise or power supply distortion.
Applies to: Inverter pair wall mounted FTXM-W/V, outdoor unit power supply
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 112. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.