Daikin · Heat pump troubleshooting

Low voltage communication wiring and thermostat connection

DX6VSDZ6VSDZ6VSA

What is going on

The unit works in a fully communicating system with a Daikin approved communicating thermostat and communicating indoor unit, using up to four wires. The typical installation uses two data wires between the indoor and outdoor units and four wires between the indoor unit and thermostat (data 1 and 2, R and C). Do not connect power wiring to the communication terminals. Do not attach any wires to the R and C terminals on the outdoor unit. Do not connect more than two wires into a single field terminal. Use 18 AWG, or shielded twisted pair for better reliability. The communicating thermostat finds the indoor and outdoor units when power is applied. Allowable maximum lengths printed are 250 and 125 (unit not legible in extracted text).

Likely causes

  • Reversed or loose communication wires causing communication error
  • More than two wires in a single terminal

Check in this order

  1. Connect data line 1 and data line 2 from the outdoor unit to terminals 1 and 2 on the indoor unit and thermostat.
  2. Connect indoor C to thermostat C and indoor R to thermostat R. Confirm wires are not reversed.
  3. Leave the R and C terminals on the outdoor unit unconnected.
  4. Never connect power wiring to communication terminals 1, 2, R or C.
  5. Keep no more than two wires in any single field terminal.
  6. Curl the end of each lead and strip only to the marked point.
  7. Confirm each wire stays in its terminal after all connections are made.
  8. Use a removable plug connector on 3.5-5.0 ton FIT and 3.0-4.0 ton Enhanced Capacity FIT units.

Applies to: Communicating system wiring for DX6VS / DZ6VS / DZ6VSA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 21-22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.