Carrier · Heat pump troubleshooting

Joint leak test

D5CURA

What is going on

Field-made joints must be leak tested with a detector sensitive to 1/8 oz (5 g) per year of refrigerant or better.

Check in this order

  1. Use a detector rated to 1/8 oz (5 g) per year or better.
  2. Test joints at standstill and under operation.
  3. Test indoor field-made joints at 125% of maximum allowable pressure. No leak is allowed.
  4. Use leak detection fluids without chlorine-based detergents.

Applies to: Field refrigerant joints

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA installation manual, p. 4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.