Carrier · Heat pump troubleshooting
IPM continuity check
What is going on
Check the power module (IPM) with a digital tester in diode/resistance mode.
Check in this order
- Turn off the outdoor unit and disconnect the power supply.
- Discharge the electrolytic capacitors and make sure all stored energy is discharged.
- Disassemble the outdoor PCB or the IPM board.
- Measure the resistance between P and U(V, W, N), and between U(V, W) and N.
- Compare with the reference values in Table 10 (values not legible in this extract).
Applies to: D5CURA outdoor unit IPM board
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA service manual, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.