Daikin · Heat pump troubleshooting
Inverter output overcurrent or compressor start failure (Checks 15, 17, 18, 22)
What is going on
Use when the outdoor unit stops on an inverter output overcurrent or the compressor fails to start. The flowchart text is out of order in this extraction, so the order below is reconstructed from the chart and the step text.
Likely causes
- Momentary drop in supply voltage
- Compressor overload
- Short circuit or wire breakage between compressor coil phases
- Wrong internal wiring after parts were disconnected and reconnected
- Faulty power module on the main PCB
Check in this order
- Turn off the power before connecting or disconnecting any connector, or parts may be damaged.
- Check that the stop valve is fully open.
- Check that the supply voltage is at rated value. Monitor voltage, discharge and suction pressures over a longer period if needed.
- Turn the power off, wait, then turn it back on to restart. See if the same error returns.
- Check the connectors and other components. Check the installation condition.
- If the system was interrupted after reconnecting wires, check the internal wiring again.
- Turn off the power and disconnect harnesses U, V and W from the compressor. Check for a short or wire breakage between the compressor coil phases. If found, replace the compressor.
- Check the power module with the inverter analyzer (Check 22). If the power module is faulty, replace the outdoor unit main PCB.
- If the error still occurs after correcting the supply, replace the outdoor unit main PCB.
- If the discharge pressure check is needed, go to Check 18. If no fault is found, treat it as not a malfunction and keep observing.
Applies to: Outdoor unit inverter circuit, 09/12 and 18/24 class
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 144-145. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.