Daikin · Heat pump troubleshooting

Inverter analyzer check of compressor and power module (Check 15)

FTXM-W/V

What is going on

Replaces the compressor with the inverter analyzer RSUK0917C to tell whether the fault is in the compressor or the drive.

Likely causes

  • Faulty compressor
  • Faulty power module
  • Solder cracks on the main PCB

Check in this order

  1. Turn the power off.
  2. Make sure the smoothing capacitor voltage has dropped to 10 VDC or below.
  3. Remove the compressor terminals. If they are not FASTON terminals, connect site wires from the PCB output side instead. Do not connect both at the same time.
  4. Connect the inverter analyzer terminals U, V and W to the compressor terminals. Keep the terminals from touching each other.
  5. Turn the power on. Select FAN mode with the Mode button on the remote controller.
  6. Start the power transistor test from the indoor unit (see the related tip).
  7. Read the 6 LEDs on the analyzer. If all LEDs light evenly, replace the compressor.
  8. If the LEDs are not even, check the power module (Check 22). If the power module is faulty, replace the main PCB, because the power module is built into it.
  9. If the power module is good, inspect the PCB for solder cracks. Repair the solder or replace the PCB if cracks are found. If none, replace the PCB.
  10. After the analyzer test, re-crimp the FASTON terminals. Loose terminals can burn.

Applies to: Compressor and inverter power module

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 150-151. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.