Daikin · Heat pump troubleshooting
Interpret target vs actual discharge temperature
What is going on
Compare the target discharge temperature with the actual discharge temperature in D-Checker to judge the refrigerant charge.
Likely causes
- Target discharge temperature higher than actual can mean an overcharge.
- Actual discharge temperature higher than target can mean an undercharged system.
Check in this order
- Wait for D-Checker to calculate the target discharge temperature (up to about 20 minutes).
- Compare target and actual discharge temperature.
- If target is higher than actual, check for an overcharge.
- If actual is higher than target, check for an undercharge.
Applies to: Daikin inverter heat pump outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EB service instructions, p. 134. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.