Daikin · Heat pump troubleshooting
Installation condition check (Check No.17)
What is going on
Flow check for poor outdoor unit airflow or heat exchanger problems caused by the installation site.
Likely causes
- Airflow blocked by obstacles
- Wind blowing against the airflow direction
- Discharge air short-circuiting back to the intake
- Dirty outdoor heat exchanger
- Outdoor temperature outside the operating range
Check in this order
- Check that the air suction and discharge clearances are within the allowable dimensions.
- If not, change the installation location or direction.
- Check whether obstacles or opposing wind block the airflow. If yes, change the installation location or direction.
- Check whether discharged air is short-circuiting. If yes, change the installation location or direction.
- Check whether the outdoor heat exchanger is very dirty. If yes, clean it.
- Check the outdoor temperature. It must be within the operation range.
Applies to: Outdoor unit installation site
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual, p. 153. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.