Installation condition check (Check No.17)

FTXM-W/V

What is going on

Flow check for poor outdoor unit airflow or heat exchanger problems caused by the installation site.

Likely causes

  • Airflow blocked by obstacles
  • Wind blowing against the airflow direction
  • Discharge air short-circuiting back to the intake
  • Dirty outdoor heat exchanger
  • Outdoor temperature outside the operating range

Check in this order

  1. Check that the air suction and discharge clearances are within the allowable dimensions.
  2. If not, change the installation location or direction.
  3. Check whether obstacles or opposing wind block the airflow. If yes, change the installation location or direction.
  4. Check whether discharged air is short-circuiting. If yes, change the installation location or direction.
  5. Check whether the outdoor heat exchanger is very dirty. If yes, clean it.
  6. Check the outdoor temperature. It must be within the operation range.

Applies to: Outdoor unit installation site

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 153. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.