Daikin · Heat pump troubleshooting

Indoor fan motor wiring check (Check 03)

FTXM-W/V

What is going on

Checks the indoor DC fan motor wiring and winding for an open or short.

Likely causes

  • Loose or bad connector
  • Broken or shorted fan motor wire

Check in this order

  1. Check that the fan motor connector is fully seated.
  2. Turn the power off.
  3. Measure resistance between phases U-V and V-W and compare with the fan motor resistance table.
  4. Replace the fan motor or repair the wiring if a reading is out of range.

Applies to: Indoor fan motor (DC motor)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 147. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.