Daikin · Heat pump troubleshooting
Indoor fan motor wiring check (Check 03)
What is going on
Checks the indoor DC fan motor wiring and winding for an open or short.
Likely causes
- Loose or bad connector
- Broken or shorted fan motor wire
Check in this order
- Check that the fan motor connector is fully seated.
- Turn the power off.
- Measure resistance between phases U-V and V-W and compare with the fan motor resistance table.
- Replace the fan motor or repair the wiring if a reading is out of range.
Applies to: Indoor fan motor (DC motor)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 147. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.