Carrier · Heat pump troubleshooting

How to read the heating capacity tables (D5CURA + D5FULA)

D5CURA

What is going on

Pages 88-90 give heating capacity and power input for the 48K and 54K heating tables. Each airflow block lists outdoor dry bulb temperature rows and indoor dry bulb columns from 60.8°F to 75.2°F.

Check in this order

  1. Find the table for your model and airflow (Table 43 on p. 88, Tables 44 and 45 on pp. 89-90).
  2. Select the airflow (CFM) block that matches the installed indoor unit.
  3. Find the outdoor DB row that matches the design outdoor temperature.
  4. Read TC (total heating capacity, BTU/hr) in the column for the indoor DB temperature.
  5. Read PI (power input, kW) from the paired column next to TC for the same indoor DB.

Applies to: D5CURA + D5FULA heating performance, 48K and 54K sizes

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA Product Data, p. 88-90. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.