How to read the cooling capacity tables (D5CURA + D5MUWA)
What is going on
Pages 91-96 give cooling capacity, sensible ratio and power input for D5MUWA indoor units. The highlighted data is tested; other values are simulated for reference.
Check in this order
- Find the table for your size (18K on pp. 92-95, 24K on p. 96) and the airflow block (CFM).
- Find the outdoor DB row that matches the design outdoor temperature.
- Read TC (total cooling capacity, BTU/hr) for the indoor WB and DB columns.
- Read S/T (sensible cooling capacity ratio) from the row under TC.
- Read PI (power input, kW) from the row under S/T.
- Treat values that are not highlighted as simulated reference data.
Applies to: D5CURA + D5MUWA cooling performance, 18K and 24K sizes
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5CURA Product Data, p. 91-96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.