Daikin · Heat pump troubleshooting

High voltage wiring and grounding precautions

DX6VSDZ6VSDZ6VSA

What is going on

Disconnect all power before servicing. Several power sources may be present. Wiring must follow NEC or CEC and local codes. Undersized wire can cause poor performance, damage or fire. Use copper conductors only. Never fit a phase-advancing capacitor, because the unit has an inverter. Do not change protection devices. Do not connect the ground wire to a gas line, sewage pipe, lightning rod or telephone ground.

Likely causes

  • Undersized wiring
  • Phase-advancing capacitor fitted to inverter unit
  • Protection devices bypassed or changed

Check in this order

  1. Disconnect all power and check for multiple power sources before servicing.
  2. Use copper conductors sized per NEC, CEC and local codes.
  3. Route power and ground through the high voltage port per the wiring diagram.
  4. Use a round crimp-style terminal on stranded wires, placed up to the insulated part.
  5. On a single core wire, curl the end of the lead and strip only to the marked point.
  6. Tighten terminal screws to the torque table value.
  7. Secure wires so outside force does not reach the terminal board.
  8. Do not fit a phase-advancing capacitor.
  9. Do not change protection device settings or fit non-Daikin parts.
  10. Reconnect all grounding wires, screws, straps, clips, nuts and washers to their original positions after any servicing.

Applies to: Power supply wiring to the outdoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 19-20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.