Daikin · Heat pump troubleshooting

High pressure switch actuation, code E3

FTXM-WFTXM-V

What is going on

The high pressure switch contact opens. Activating pressure is 4.15 MPa and recovery pressure is 3.2 MPa.

Likely causes

  • High pressure switch (S1PH) activated
  • Stop valve closed
  • Connector S40 disconnected
  • Two terminals of S1PH disconnected
  • Defective outdoor unit PCB
  • Broken S1PH harness
  • Defective high pressure switch (S1PH)

Check in this order

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check that the stop valve is open. If closed, open it.
  3. Check that connector S40 is properly connected. If not, reconnect it.
  4. Measure the resistance between pins 1 and 2 on connector S40. Nearly 0 Ω is normal. Infinite resistance means a fault.
  5. If the reading is infinite, disconnect connector S40 from the PCB and replace the harness for the high pressure switch if it is faulty.
  6. Disconnect the two terminals of the high pressure switch (S1PH).
  7. Measure the resistance across the two terminals of S1PH. Nearly 0 Ω is normal.
  8. If S1PH reads infinite, replace the high pressure switch (S1PH).
  9. If the harness and switch are good but the fault remains, replace the outdoor unit PCB (main PCB).

Applies to: Inverter pair wall mounted FTXM-W/V, outdoor unit high pressure circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 117. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.