Daikin · Heat pump troubleshooting

Heating emergency mode - EEV cased coil with gas furnace or modular blower

DX6VS / DZ6VS Inverter outdoor units with CHPE EEV cased coils

What is going on

The gas furnace or modular blower alone runs the heat. The outdoor unit stays off in this mode.

Check in this order

  1. Turn off power to all equipment.
  2. Remove the thermostat communication wires (1, 2, R, C) from every connected unit: EEV cased coil, gas furnace or modular blower, outdoor unit and thermostat. The terminals are on each unit's control board.
  3. Reconnect the wires to the communication terminal of the gas furnace or modular blower and short-circuit the terminal with the wires so the furnace or blower runs on its own. Check its service manual for the connection points.
  4. On the EEV cased coil control board, set DS-6 S-21 to OFF and S-22 to ON for heating emergency mode.
  5. Power the equipment on. Heating emergency starts. No DIP setting is needed in the outdoor unit.
  6. After communication is restored, set the cased coil DS-6 switches back to default and restore all thermostat wiring.

Applies to: CHPE cased coil with gas furnace or modular blower

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.