Heating analysis: possible causes and remedies
What is going on
Use the heating analysis chart when readings fall outside the listed thresholds or when defrost is incomplete.
Likely causes
- Liquid or gas stop valve not fully open
- Line set restriction or line set too long
- Blocked filter-dryer
- Outdoor EEV coil or EEV failure
- Indoor EEV coil or EEV failure
- Outdoor solenoid valve coil or valve failure
- Check valve leakage
- High pressure switch failure
- Pressure sensor failure
- Outdoor suction, discharge, coil, coil defrost, liquid or air thermistor failure
- Outdoor or indoor air recirculation
- Dirty outdoor or indoor heat exchanger
- Outdoor or indoor return air temperature out of range
- Non-condensable gas in system
- Outdoor fan motor failure
- Reversing valve (RV) or RV coil failure
- Overcharge or undercharge; leak
- Indoor unit failure; outdoor control board failure
- Compressor failure
- Low indoor CFM
Check in this order
- Fully open the liquid stop valve and gas stop valve.
- Check the line set for restrictions and length; change outdoor position if needed.
- Replace the filter-dryer if blocked.
- Check outdoor and indoor EEV coil connections and EEV operation; repair or replace as needed.
- Check the outdoor solenoid valve, its coil and the check valve; repair or replace as needed.
- Check high pressure switch resistance; replace if needed.
- Check pressure sensor and thermistor resistance and connections; replace if needed.
- Re-arrange outdoor or indoor unit position to stop recirculation.
- Clean outdoor or indoor heat exchanger.
- Recover refrigerant, evacuate the pipe and recharge if non-condensable gas is present.
- Replace outdoor fan motor if failed.
- Check reversing valve and its coil; repair or replace as needed.
- Recover part of charge if overcharged; test for leaks and add refrigerant if undercharged.
- Find and repair the leak point.
- Replace indoor unit, outdoor control board or compressor if failed.
- Check airflow trim and indoor fan motor; repair or replace as needed.
Applies to: DX6VS/DZ6VS outdoor units in heating
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EB service instructions, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.