Daikin · Heat pump troubleshooting

Heating analysis chart

DX6VSDZ6VS

What is going on

Use the readings to find the likely cause. Normal outdoor range for heating analysis is 17-62 F. Normal indoor range is 65-85 F.

Likely causes

  • Discharge temperature above 200 F or below 105 F
  • Discharge superheat above 80 F or below 20 F
  • High pressure above 490 psig
  • High pressure at SSV or LSV below 270 psig
  • Low pressure below 40 psig
  • Repeated stop/start, weak heating, no switch heating, noise, incomplete defrost, stop operation, sweating liquid line
  • Stop valve not fully open, line set restriction or too long, blocked filter-dryer, OD or ID EEV faults, check valve leakage, sensor faults, dirty coils, recirculation, out-of-range ambient, non-condensible gas, fan or reversing valve faults, over or under charge, leak, control board or compressor failure, low indoor CFM

Check in this order

  1. Fully open the liquid and gas stop valves.
  2. Check the line set for restriction and length. Change OD position if needed.
  3. Replace the filter-dryer if it is blocked.
  4. Check the OD and ID EEVs and their coils. Repair or replace as needed.
  5. Check the check valve for leakage and repair or replace if needed.
  6. Check the RV and RV coil. Repair or replace as needed.
  7. Check the sensors and their connections. Replace if needed.
  8. Clean dirty outdoor or indoor heat exchangers.
  9. Recover refrigerant, evacuate and recharge if non-condensible gas is present.
  10. Recover part of the charge if overcharged; test for leaks and add refrigerant if undercharged.
  11. Check the indoor fan motor and airflow if CFM is low.

Applies to: DX6VS/DZ6VS outdoor unit, heating mode

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS outdoor unit installation manual, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.