Daikin · Heat pump troubleshooting
Heating analysis chart: possible causes and remedies
What is going on
Use the heating analysis chart when the unit shows high or low discharge temperature, pressure or superheat, repeated stop/start, weak heating, no heating, incomplete defrost, sweating liquid line or noise. Normal heating range: outdoor 17-62 F, indoor 65-85 F.
Likely causes
- Liquid stop valve not fully open
- Gas stop valve not fully open
- Line set restriction
- Line set too long
- Blocked filter-dryer
- Outdoor EEV coil failure
- Outdoor EEV failure
- Indoor EEV coil failure
- Indoor EEV failure
- Outdoor solenoid valve coil failure
- Outdoor solenoid valve failure
- Check valve leakage
- High pressure switch failure
- Pressure sensor failure
- Outdoor suction thermistor failure
- Outdoor discharge thermistor failure
- Outdoor coil thermistor failure
- Outdoor coil defrost thermistor failure
- Outdoor liquid thermistor failure
- Outdoor air thermistor failure
- Outdoor air recirculation
- Indoor air recirculation
- Dirty outdoor heat exchanger
- Dirty indoor heat exchanger
- Outdoor ambient temperature too high or too low
- Indoor return air temperature too high or too low
- Non-condensable gas in system
- Outdoor fan motor failure
- RV (reversing valve) failure
- RV coil failure
- Overcharge
- Undercharge
- Refrigerant leak
- Indoor unit failure
- Outdoor control board failure
- Compressor failure
- Cooling loop not attached to cold plate
- Cooling loop grease insufficient
- Low indoor CFM
Check in this order
- Fully open the liquid stop valve.
- Fully open the gas stop valve.
- Check the line set for restriction; check line set length and change outdoor position if needed.
- Replace the filter-dryer if blocked.
- Check the outdoor EEV coil connection; repair or replace if needed.
- Check the outdoor EEV; repair or replace if needed.
- Check the indoor EEV coil connection to the control board; repair or replace if needed.
- Check the indoor EEV; replace or repair if needed.
- Check the outdoor solenoid valve coil connection; repair or replace if needed.
- Check the outdoor solenoid valve; replace or repair if needed.
- Check the check valve for leakage; repair or replace if needed.
- Check the high pressure switch resistance; replace if needed.
- Check the pressure sensor resistance and connections; replace if needed.
- Check the outdoor thermistors (suction, discharge, coil, coil defrost, liquid, air) for resistance and connections; replace if needed.
- Re-arrange the outdoor unit position if air is recirculating.
- Re-arrange the indoor unit position if air is recirculating.
- Clean the outdoor and indoor heat exchangers.
- Recover refrigerant, evacuate the pipe and recharge if non-condensable gas is present.
- Replace the outdoor fan motor if it has failed.
- Check the reversing valve; repair or replace if needed.
- Check the reversing valve coil; repair or replace if needed.
- Recover part of the charge if overcharged.
- Test for leaks and add refrigerant if undercharged.
- Find and repair the leak point.
- Replace the indoor unit if it has failed.
- Replace the outdoor control board if it has failed.
- Replace the compressor if it has failed.
- Attach the cooling loop to the cold plate.
- Add grease to the cooling loop if insufficient.
- Check airflow trim and indoor fan motor; repair or replace if needed.
Applies to: DX6VS / DZ6VS heat pump in heating
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.