Trane · Heat pump troubleshooting
Heat pump wiring notes (third-party condensate switch and X2 for defrost)
What is going on
Wiring notes that apply to the heat pump wiring diagrams on pages 5 to 7.
Check in this order
- Wire any third-party condensate overflow switch in series between thermostat Y and the airflow control board Y1.
- Run X2 to energize auxiliary heat during defrost.
- Use the diagram that matches the indoor unit and outdoor unit, such as TAM series, S9V2 furnace, variable speed gas furnace, GAT2/GAM2/TEM3/TEM4 or GAM5A/TAM4/GAF2-36M.
Applies to: Heat pump systems with XR103 thermostat
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 5-7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.