BK output wiring with variable speed indoor unit
What is going on
The BK output sends a PWM airflow signal to a variable speed indoor unit. It needs the factory BK jumper removed at the indoor unit and the R-to-BK jumper cut at the control.
Check in this order
- Cut or remove the R-to-BK jumper at the control.
- Set the indoor unit dip switches 5 and 6 to OFF.
- Leave the Y terminals on the indoor unit disconnected.
- Add a BK wire from the control to the variable speed indoor unit.
Applies to: BK output enabled systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.