Trane · Heat pump troubleshooting

Defrost heater balance point control

XR402

What is going on

Each installed heater stage can have its own outdoor temperature threshold for defrost. If not enabled, that heater stage energizes every defrost cycle regardless of outdoor temperature. After defrost, load calculation resumes duty cycle control of the heater stages. During defrost the heat pump is not cycled off unless indoor temperature overshoots the heating setpoint by 2.5 degrees or more.

Check in this order

  1. Set an outdoor temperature threshold for each installed heater stage used in defrost, or leave a stage without a threshold if it should run every defrost.
  2. Confirm the outdoor sensor is installed and enabled.
  3. Check that heater stages cycle normally after defrost ends.

Applies to: Heat pump with electric heat stages and TCONT402AN32DA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.