Trane · Heat pump troubleshooting

Auxiliary heat lockout by outdoor temperature

XR402

What is going on

Auxiliary heat lockout is set with an outdoor temperature. No installed auxiliary heat stage turns on during heating above that temperature. During defrost this setting is ignored and the Defrost Heater Balance Point thresholds are used instead. Requires the outdoor sensor.

Check in this order

  1. Confirm the outdoor sensor is installed and enabled.
  2. Set the auxiliary heat lockout outdoor temperature in the installer setup.
  3. Check that no auxiliary heat stage runs above the set temperature during heating.

Applies to: Heat pump with auxiliary heat and TCONT402AN32DA

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD29D3-4 installer's guide, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.