Cooling lockout in cold outdoor temperature

XR103

What is going on

Compressor protection rule for cooling operation below 55°F outdoors.

Likely causes

  • Outdoor temperature is below 55°F.
  • Compressor oil heaters have not been energized for six hours.
  • System was running less than five minutes before the restart attempt.

Check in this order

  1. Do not run the cooling system when outdoor temperature is below 55°F.
  2. Confirm the compressor oil heaters have been on for six hours before allowing compressor operation.
  3. Confirm the system has been off for at least five minutes before restarting the compressor.

Applies to: Heat pump systems using the XR103 thermostat

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR103 installation and user guide 18-HD55D1-1C-EN, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.