Carrier · Heat pump troubleshooting

Heat pump will not defrost - HK32EA defrost board

What is going on

Outdoor coil ices up and the unit never shifts into defrost.

Likely causes

  • Defrost thermostat failed or loose on stub tube
  • No 24 V on T1
  • Bad thermostat pigtail or wiring
  • Failed board

Check in this order

  1. Run a forced defrost with the speed-up pins; if it defrosts, the board is fine and the defrost thermostat is suspect.
  2. No defrost on speed-up check 24 V on T1 - it powers the defrost timing.
  3. Test the defrost thermostat with an ohmmeter while frost builds: it should close near 32 F (33-27 F) and open about 60-70 F after defrost.
  4. Confirm the defrost thermostat sits on the bottom-circuit liquid stub tube and the cup material matches the tube.
  5. During defrost check 24 V between C and W2.
  6. Still no defrost unplug the pigtail and jumper the board inputs directly; a bad pigtail is common.

Applies to: Carrier/Bryant heat pumps with HK32EA boards

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier Residential AC & HP Application Guideline and Service Manual 24-25-9SM (text export), Defrost Speedup and Check Defrost Thermostat. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.