Heat exchanger removal (1.5 to 3.0 ton)
What is going on
Removal of the outdoor coil heat exchanger on 1.5 to 3.0 ton HP and AC units. The brazed joints are heated, so protect the surroundings first.
Check in this order
- Remove the old putty first, since it can burn during brazing.
- Put a protective sheet or steel plate in place so the brazing flame cannot reach nearby parts.
- Remove the suction grille (1 screw).
- Remove 4 screws and take off the left side plate.
- Heat the brazed joints and remove the heat exchanger.
Applies to: 1.5 to 3.0 ton HP & AC outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 104. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.