Daikin · Heat pump troubleshooting
Freeze-up protection in cooling
What is going on
In cooling, the indoor unit signal sets the outdoor frequency upper limit based on indoor heat exchanger temperature, to stop the coil from freezing. The indoor temperature band is split into stop, dropping, keep, up and reset zones. The exact zone temperatures appear only in the diagram, so read them from the figure on page 80 rather than from the text.
Likely causes
- Indoor heat exchanger temperature falls too low during cooling
Check in this order
- Read the indoor heat exchanger temperature (R2T).
- Check which zone it falls in stop, dropping, keep, up or reset.
- In stop zone, the compressor stops; in dropping zone, the frequency upper limit is lowered; in keep zone, it is held; in up zone, it is raised; in reset zone, the limit is cancelled.
Applies to: FTXM-W/V wall mounted heat pump, cooling operation
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.