Four-way valve performance check (Check 13)
What is going on
Checks the four-way valve coil and its drive voltage on S80 during heating start.
Likely causes
- Open or shorted four-way valve coil
- Faulty four-way valve
- Faulty outdoor unit main PCB drive
Check in this order
- Start heating operation.
- Check the four-way valve coil resistance. If it is not 440 to 750 Ω, replace the coil.
- Measure voltage at S80 with the compressor on. If it reads 0 VDC, check the drive circuit and replace the main PCB if needed.
- Check that S80 reads 120 to 380 VDC for about 3 seconds after compressor start, then drops to about 10 to 24 VDC. If not, replace the main PCB.
- If the coil is good and voltage is correct but the valve still fails, replace the four-way valve.
- Coil continuity check cooling or dry mode shows no continuity; heating mode shows continuity.
- Caution wait 30 seconds or more after turning the power off before turning it back on.
Applies to: Four-way valve coil and S80 drive
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 149. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.