Daikin · Heat pump troubleshooting

Four-way valve performance check (Check 13)

FTXM-W/V

What is going on

Checks the four-way valve coil and its drive voltage on S80 during heating start.

Likely causes

  • Open or shorted four-way valve coil
  • Faulty four-way valve
  • Faulty outdoor unit main PCB drive

Check in this order

  1. Start heating operation.
  2. Check the four-way valve coil resistance. If it is not 440 to 750 Ω, replace the coil.
  3. Measure voltage at S80 with the compressor on. If it reads 0 VDC, check the drive circuit and replace the main PCB if needed.
  4. Check that S80 reads 120 to 380 VDC for about 3 seconds after compressor start, then drops to about 10 to 24 VDC. If not, replace the main PCB.
  5. If the coil is good and voltage is correct but the valve still fails, replace the four-way valve.
  6. Coil continuity check cooling or dry mode shows no continuity; heating mode shows continuity.
  7. Caution wait 30 seconds or more after turning the power off before turning it back on.

Applies to: Four-way valve coil and S80 drive

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 149. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.