Trane · Heat pump troubleshooting

Forcing a defrost - Trane 5TWR7

What is going on

Forced defrost on the Trane 5TWR7 multi-speed heat pump. Use it to see whether the board can actually run a defrost cycle when the coil is iced. Unit has to be in heating and calling. Does nothing in cooling. Normal demand defrost only arms in cool outdoor air after a set heat call time.

Likely causes

  • Coil iced and you need to verify defrost
  • Complaint of ice build-up on the outdoor coil
  • Checking defrost after replacing a sensor or board
  • Defrost seems to end too early

Check in this order

  1. Unit must be running in heating with a thermostat call, forced defrost does not work in cooling
  2. Hold the board's forced defrost button down for over 5 s
  3. Display shows 7 as the first digit while defrosting
  4. Watch the outdoor fan stop and the reversing valve shift, and see whether ice clears
  5. Normal demand defrost only arms when outdoor ambient is at or below 50 F and there has been a heat call for a set time
  6. If defrost ends too early, clipping the defrost termination jumper raises the termination temperature
  7. Power off before working on the board or jumper

Applies to: Trane 5TWR7024A-060A

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7 installer's guide) - section Defrost Control. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.