Carrier · Heat pump troubleshooting

Fan motor checks (indoor and outdoor DC fan motors)

D5FUAA

What is going on

Checks for the indoor and outdoor DC fan motors used in fan speed faults.

Check in this order

  1. Indoor DC fan motor (control chip is in the fan motor): with power on and unit in standby, measure the voltage from pin 1 to pin 3 and pin 4 to pin 3 at the fan motor connector. If not in the range in the pin table, replace the PCB.
  2. Outdoor DC fan motor (control chip is in the outdoor PCB): release the UVW connector and measure resistance U-V, U-W and V-W.
  3. If the resistances are not equal to each other, replace the fan motor.
  4. If the resistances are equal, replace the PCB.

Applies to: D5FUAA indoor and outdoor fan motors

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUAA Service Manual, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.