Daikin · Heat pump troubleshooting
Fan and fan motor removal (3.5 to 5.0 ton)
What is going on
Removal of the outdoor fan, fan motor stand and fan motor, with the lead wire routing that must be restored on reassembly.
Check in this order
- Disconnect the fan motor connector (X108A) and release the lead wire from the hooks.
- Remove the M8 nut and take off the fan.
- Remove 2 screws and take off the fan motor stand.
- Remove 4 screws (M5 x 25 tapping screws) and take off the fan motor.
- On reassembly, lower the partition plate hook to pass the lead wire through, then return the hook.
- Clamp the motor lead no more than 10 mm from the partition plate, using a weather resistant tie on the motor stand.
- Route the lead behind the fan motor stand on 3.5/4.0 ton units and in front of it on 5.0 ton units, to keep it clear of the outdoor fan.
Applies to: 3.5 to 5.0 ton HP & AC outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, pp. 109-110. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.